Mitsubishi Electric P4 Error, Drain Sensor and Float Switch

Ceiling cassettes and many ducted units cannot rely on gravity alone to get rid of the water they make, so they use a pump and a sensor that watches the water level.

The Mitsubishi Electric P4 error points to trouble with that sensor or float switch. This guide explains the code, the checks and the fixes.

What does the Mitsubishi Electric P4 code mean?

When an air conditioner cools, moisture from the room condenses on the indoor coil and drips into a tray. Units mounted in ceilings often sit lower than the place the water needs to go, so a small pump lifts it out. Next to that pump, a float switch or drain sensor keeps watch over the water level in the tray.

On many Mitsubishi Electric models, service information links P4 to the drain sensor or float switch circuit. Depending on the model, it may mean the sensor itself has failed, its connection has a fault or it is reporting a water level that the board cannot accept. Either way, the board stops the system to avoid water spilling into your ceiling. Ceilings are expensive to repair, so the designers chose to stop early rather than risk a leak above your furniture.

Where P4 usually shows up

P4 is mainly a code for units with a drain pump. That includes ceiling cassettes, many bulkhead and ducted units and some ceiling suspended units. A standard high wall split usually drains by gravity and may not have a float switch, so it tends to drip rather than show P4.

How does P4 present itself?

Look out for these signs, which often show up before or alongside the code.

  • The system stops and the wired controller shows P4.
  • Water stains appear on the ceiling around a cassette or near a ducted unit.
  • A musty or swampy smell hangs around the outlet grilles.
  • You hear the drain pump running constantly, or never at all.
  • The fault appears mostly on humid days.

If water is dripping through a ceiling, switch the system off at the controller straight away and protect the area below with towels or a bucket.

What causes the P4 fault?

The causes fall into two groups. Some involve water genuinely building up. Others involve the sensor saying there is water when there is not.

Slime and sludge in the tray

Dust, skin cells and mould mix with condensate to form slime. Over time, that slime builds up in the tray and around the float. A float coated in sludge may stick in the raised position, which makes the board think the tray is full.

A blocked drain line

The line that carries water away can block with the same slime, or with insects and debris at the outside end. Water then backs up into the tray, lifts the float and triggers the fault.

A weak or failed drain pump

If the pump cannot keep up or has stopped, water rises. On some models, a pump failure shows as its own code, P5, while on others the rising water triggers P4 first.

A faulty float switch or sensor

The float switch is a simple part, yet it can fail. Its magnet or contacts can wear, its lead can break and its plug can corrode in the damp environment above the tray.

Problems with the drain route

A drain line that rises after the pump, sags in the ceiling or runs too flat lets water flow back. Renovations sometimes disturb these lines without anyone noticing, for example when electricians or plumbers move things around in the ceiling space to reach their own work.

What can you check yourself?

Most drain parts sit inside the ceiling, so your role is limited to the outside of the system.

  1. Turn the system off with the controller.
  2. Check the ceiling around the unit for wet patches and protect anything underneath.
  3. Find where the drain line ends outside and check that it is not blocked by soil, leaves or insects.
  4. Clean any filters you can reach safely, because dirty filters can lead to coil freezing and sudden meltwater.
  5. Wait a while with the system off, then try once more and see whether P4 returns.

Our guide to cleaning Mitsubishi Electric filters explains filter care, and our page on a Mitsubishi Electric leaking water covers leaks in more detail.

Do not keep restarting with a full tray

Each restart can push more water into a tray that is already full, raising the risk of a ceiling leak. If P4 returns, leave the system off until a technician has looked at it.

How does a technician clear a P4 fault?

The technician works through the drain system in a logical order, starting at the tray.

Checking the water level

First, they open the unit and look at the tray. A full tray points to a drainage problem, while a dry tray points to the sensor or its wiring.

Cleaning the tray and float

Next, they clear slime from the tray and the float so it can move freely. Many technicians also treat the tray to slow the return of slime.

Testing the pump

After that, they pour water into the tray and watch whether the pump lifts it away. A pump that hums but moves little water may have a clogged inlet or a failing motor. Sometimes cleaning the inlet screen brings a sluggish pump back to life, while a worn motor needs replacing.

Clearing the drain line

They then flush or blow out the drain line and check its fall all the way to the outlet. Sags, kinks and uphill sections all need correcting.

Testing the float switch

Finally, they check that the float switch changes state as it rises and falls, and that the board reads it correctly. A failed switch or lead needs replacing.

How serious is P4?

It can become serious quickly if water reaches the ceiling. Wet plasterboard can sag, stain and grow mould, and water near light fittings is a hazard. Fortunately, the float switch exists to stop the system before that happens. If you switch off promptly, most P4 faults cause little damage, and the repair is often just cleaning.

How does P4 compare with nearby codes?

Mitsubishi Electric drain and coil codes
CodeUsual meaning
P4Drain sensor or float switch fault, or high water detected
P5Drain pump fault
P6Coil freezing or overheating protection

Freezing can produce sudden meltwater that overwhelms the tray, so a P6 history is worth mentioning.

Why does P4 often appear in humid weather?

Muggy days mean the coil pulls a lot of water from the air. A drain that copes on a dry day can fall behind when the flow doubles. As a result, P4 often turns up during the first sticky week of summer or after a run of storms. A drain flush and pump test before summer reduces that risk.

Can a smell warn you before P4?

Often. Still water in a tray grows slime and bacteria quickly, and the fan spreads the smell into the room. Many homes notice a swampy or sour odour weeks before the code appears. Acting on the smell early lets a technician clean the tray before the float sticks. Our guide on a Mitsubishi Electric AC that smells bad explains more.

What about ducted systems in the roof?

Ducted units often sit above living areas, so a drain fault can soak through quickly. Some installations include a secondary safety tray under the unit with its own float or outlet. If your ducted system shows P4, switch it off and check the ceiling below the roof unit. Our ducted page explains ducted care.

Can a new installation cause P4?

Yes. On a new system, the pump lift may be too high for the pump, the drain line may rise after the pump or building dust may already be in the tray. If P4 appears soon after installation, contact the installer first. Our installation page explains what good drain design looks like.

How does a float switch work?

A float switch is a simple idea. A small buoyant piece sits in the tray and rides up and down with the water. Inside or beside it, a magnet or contact changes state when the float rises past a set point. The board reads that change as a warning that water is too high.

Because the design is so simple, most problems come from the environment rather than the switch itself. Slime glues the float in place, debris jams it or corrosion attacks the contacts. Cleaning and freeing the float solves a large share of P4 faults without any new parts.

What does a healthy drain pump sound like?

Most drain pumps make a soft whirr while running and stop once the tray empties. On many units, the pump keeps running for a short time after cooling stops, to clear the last of the water. A pump that runs nonstop, makes a loud rattle or never seems to run at all deserves a check.

Some owners also hear gurgling as air and water move through the line. Occasional gurgles are normal. Constant gurgling with a smell, however, usually means the line is partly blocked.

Where does the water go outside?

The drain line usually ends near a gutter, a stormwater pit or a garden bed. Over time, soil can build up around the outlet, insects can crawl inside and leaves can cover it. A blocked outlet forces water back up the line, even when everything inside the ceiling is clean.

Finding and checking the outlet is one of the most useful things you can do. If you are not sure where it is, the technician can show you during the visit so you can check it yourself in future.

Is cooling only affected?

Mostly. In heating mode, the indoor coil runs warm and produces little or no water, so P4 is rare. Some owners find their system runs fine in winter, only for the code to return in the first humid days of spring. It makes sense to fix the drain during the cooler months rather than wait.

How can you prevent P4?

A few simple habits keep drains clear and save you from water damage and unpleasant smells.

  • Clean filters regularly to prevent coil freezing.
  • Keep the outside end of the drain line clear.
  • Ask for a drain flush and pump test as part of each service.
  • Act early on smells or gurgling sounds from the ceiling.
  • Let the technician know if anyone has worked in the ceiling space.

Our service page explains what a service involves.

What helps us prepare for the visit?

  • The type of unit, such as cassette, ducted or bulkhead.
  • The model number from the unit or controller.
  • Where you have seen water, and how much.
  • Whether you can hear the drain pump running.
  • Where the ceiling access hatch is, for ducted units.

Bringing it together on the Mitsubishi Electric P4 error

The Mitsubishi Electric P4 error tells you the drain sensor or float switch has either failed or detected too much water. Slime, blocked lines, weak pumps and sticky floats are the usual culprits. Switch off, protect the area below and avoid repeated restarts.

Then book a Mitsubishi Electric technician to clean the tray, test the pump and float and clear the drain line properly.

Frequently asked questions

What does P4 mean on a Mitsubishi Electric air conditioner?

P4 usually relates to the drain sensor or float switch in units with a drain pump, either a sensor fault or high water detected.

Which units show P4?

P4 mainly appears on ceiling cassettes, ducted units and other units that use a drain pump.

Can a dirty drain tray cause P4?

Yes. Slime can stick the float in the raised position or block the drain, both of which can trigger P4.

What should I do if water is coming through the ceiling?

Switch the system off, protect the area below and book a technician as soon as possible.

Why does P4 happen in humid weather?

Humid air produces more water, and a partly blocked drain may not keep up.

Is P4 the same as P5?

No. P5 usually points to the drain pump itself, while P4 relates to the float switch or water level sensor.

{“@context”:”https://schema.org”,”@type”:”HVACBusiness”,”@id”:”https://mitsubishi.sydneyaircare.com.au/#business”,”name”:”Sydney Air Care, Mitsubishi Electric Service”,”url”:”https://mitsubishi.sydneyaircare.com.au/”,”description”:”Mitsubishi Electric air conditioner repair, service and troubleshooting across Sydney. Independent service provider, not affiliated with Mitsubishi Electric.”,”areaServed”:[{“@type”:”City”,”name”:”Sydney”},{“@type”:”State”,”name”:”New South Wales”}],”parentOrganization”:{“@type”:”Organization”,”name”:”Sydney Air Care”,”url”:”https://sydneyaircare.com.au/”},”telephone”:”+61 2 9071 1142″} {“@context”:”https://schema.org”,”@type”:”FAQPage”,”mainEntity”:[{“@type”:”Question”,”name”:”What does P4 mean on a Mitsubishi Electric air conditioner?”,”acceptedAnswer”:{“@type”:”Answer”,”text”:”P4 usually relates to the drain sensor or float switch in units with a drain pump, either a sensor fault or high water detected.”}},{“@type”:”Question”,”name”:”Which units show P4?”,”acceptedAnswer”:{“@type”:”Answer”,”text”:”P4 mainly appears on ceiling cassettes, ducted units and other units that use a drain pump.”}},{“@type”:”Question”,”name”:”Can a dirty drain tray cause P4?”,”acceptedAnswer”:{“@type”:”Answer”,”text”:”Yes. Slime can stick the float in the raised position or block the drain, both of which can trigger P4.”}},{“@type”:”Question”,”name”:”What should I do if water is coming through the ceiling?”,”acceptedAnswer”:{“@type”:”Answer”,”text”:”Switch the system off, protect the area below and book a technician as soon as possible.”}},{“@type”:”Question”,”name”:”Why does P4 happen in humid weather?”,”acceptedAnswer”:{“@type”:”Answer”,”text”:”Humid air produces more water, and a partly blocked drain may not keep up.”}},{“@type”:”Question”,”name”:”Is P4 the same as P5?”,”acceptedAnswer”:{“@type”:”Answer”,”text”:”No. P5 usually points to the drain pump itself, while P4 relates to the float switch or water level sensor.”}}]}